Thanks Crossy. See attached sketch - existing building has 10 rooms, all with their own consumer unit, and each consumer units has the earth connected to the neutral, so your comment is a bit of a concern. Should these N-E connections be removed? I don't think there is a N-E connection in the distribution board but will take a photo (by distribution board I mean where the main feed comes in and then the live and neutrals get passed to each room. The earths for rooms 1-10 connect to a MET in the distribution board).
For the new rooms (11-13) a second earth rod needs to be used since they are 20m away from the first earth rod. These 3 rooms are also closer to the main meter, so plan is to connect to it again. I sketched out the intended earth connections based on your earlier comment - all 3 earths connecting in room 11 consumer unit.